Schneider C125H420FM | Circuit breaker, ComPacT NS1250H, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 1250A

ComPacT NS is a range of circuit breakers for built-in power & energy metering
The solution covers ratings from 630 A to 3200 A
MicroLogic electronic control unit provides electrical measurement and analysis functions
ComPacT NS offers an optimized range of auxiliaries and accessories, field installable
Flexible installation, in any position, in a switchboard or wall-mounted

Schneider C125H420FM | Circuit breaker, ComPacT NS1250H, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 1250A

Product: Schneider C125H420FM

The C125H420FM is a high-performance molded case circuit breaker (MCCB) from Schneider Electric’s ComPacT NS1250H series. It is designed to protect large-scale electrical systems from overloads and short circuits, particularly in environments with high fault current levels.

Detailed Breakdown:

1. Series & Model:

  • ComPacT NS1250H

  • “1250” indicates the frame size, built to handle up to 1250A of current.

  • “H” means High breaking capacity, ideal for critical and fault-prone environments.

2. Rated Current:

  • 1250 Amps (A)

  • This is the maximum continuous current the breaker can carry without tripping.

  • Suitable for main distribution panels, large generators, or high-load feeders in industrial and commercial applications.

3. Breaking Capacity:

  • 70 kA at 415 VAC

  • This indicates the breaker can safely interrupt a fault current of up to 70,000 amps.

  • It provides reliable protection in systems with high short-circuit potential, such as near large transformers or utility feeders.

4. Number of Poles:

  • 4 Poles (4P)

  • Protects all three phases (L1, L2, L3) and the neutral conductor (N).

  • Important in systems with unbalanced loads or neutral fault risks.

5. Mounting Type:

  • Fixed

  • The breaker is installed permanently inside the electrical panel.

  • It is not withdrawable, so any maintenance or replacement requires system shutdown and manual disconnection.

6. Operation:

  • Manually Operated

  • Operated by hand using a toggle switch or rotary handle.

  • No motor mechanism for remote operation.

7. Trip Unit / Control Unit:

  • MicroLogic 2.0

  • An electronic trip unit that provides:

    • Long-time delay protection – for sustained overloads.

    • Short-time delay protection – for short-circuits.

  • The unit includes adjustable protection settings, but does not support advanced features like metering, alarms, or communication.

Typical Applications:

  • Main breaker in industrial electrical panels

  • Protection of generator or transformer outputs

  • Heavy-duty feeders in commercial or infrastructure installations

  • Systems needing complete 4-pole protection including neutral isolation

Brands

Reviews

There are no reviews yet.

Be the first to review “Schneider C125H420FM | Circuit breaker, ComPacT NS1250H, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 1250A”

Your email address will not be published. Required fields are marked *

Delivery

We ship to all 50 states, Washington DC. All orders are shipped with a UPS tracking number. Always free shipping for orders over US $200. During sale periods and promotions the delivery time may be longer than normal.

Return

Urna will accept exchanges and returns of unworn and unwashed garments within 30 days of the date of purchase (14 days during the sales period), on presentation of the original till receipt at any store where the corresponding collection is available within the country of purchase.

Your return will usually be processed within a week to a week and a half. We’ll send you a Return Notification email to notify you once the return has been completed.
Please allow 1-3 business days for refunds to be received to the original form of payment once the return has been processed.

Help

  • Give us a shout if you have any other questions and/or concerns.
  • Email: contact@mydomain.com
  • Phone: +1 (23) 456 789